Abstract

The work reported in this paper proposes a new method for detecting loss of mains (LOM), which considered one of the basic protection systems that should be provided for an embedded generator (EG). The proposed LOM protection particularly considers the case when the EG is “islanded” with part of the utility load which has a capacity close to that of the generator. It also has the capability to deal with the difficult situation related to differentiate between LOM and the loss of parallel feeder at the interfacing circuit between EG and the utility. The proposed method is based on using the rate of change of voltage (dV/dt) and the change in power factor (Δpf) measured at the interfacing point between the EG and the utility network.
Original languageEnglish
Title of host publicationProceedings of the 7th International Conference on Developments in Power Systems Protection (DPSP 2001)
Place of PublicationStevenage
PublisherIET
Pages82-85
Number of pages4
ISBN (Print)0852967322
DOIs
Publication statusPublished - Apr 2001
Event7th International Conference on Developments in Power System Protection - Amsterdam, Netherlands
Duration: 9 Apr 200112 Apr 2001
Conference number: 7

Conference

Conference7th International Conference on Developments in Power System Protection
Abbreviated titleDPSP 2001
CountryNetherlands
CityAmsterdam
Period9/04/0112/04/01

    Fingerprint

Cite this

Salman, S. K., King, D. J., & Weller, G. (2001). New loss of mains detection algorithm for embedded generation using rate of change of voltage and changes in power factors. In Proceedings of the 7th International Conference on Developments in Power Systems Protection (DPSP 2001) (pp. 82-85). IET. https://doi.org/10.1049/cp:20010105